AWG to mm Converter
A free tool by DeepRit, a Google Ads agency that does PPC and nothing else. We build and run Google Ads accounts so every click is accounted for. Book a free audit call
Convert AWG wire gauge to mm and mm² (or mm to the nearest AWG), with inches, kcmil and copper resistance. From 4/0 to 40 gauge.
- Cross-section
- 0
- Diameter in inches
- 0
- kcmil
- 0
- Copper resistance
- 0
Free, no sign-up. Runs in your browser: nothing you type is uploaded or saved.
How to use the AWG to mm converter
- Choose the direction: AWG to mm, or mm to AWG.
- For AWG to mm, enter the gauge. Use numbers such as 12 or 24, and write the large sizes as 1/0, 2/0, 3/0 or 4/0.
- For mm to AWG, enter the wire diameter in millimetres.
The converter shows the diameter in millimetres and inches, the cross-sectional area in mm² and kcmil, and the resistance of solid copper wire at 20 °C, plus a reference table of common gauges. When converting from mm, it gives the nearest AWG size.
What is AWG?
American Wire Gauge (AWG) is the standard system for sizing electrical wire in the United States and Canada, and it's used worldwide for electronics, audio and networking cables. It's a logarithmic system, standardised in ASTM B258, in which a higher number means a thinner wire. 24 AWG is a thin wire used in network cables; 12 AWG is a common size for household circuits in North America; 4/0 (pronounced "four aught") is a thick cable used for service entrances and large battery banks.
The sizes are defined by a geometric sequence: 36 AWG is exactly 0.005 inches in diameter, 4/0 is exactly 0.46 inches, and there are 39 steps between them, each a constant ratio apart.
The AWG to mm formula
Diameter (mm) = 0.127 × 92^((36 − n) ÷ 39)
where n is the gauge number. For the aught sizes, 1/0 is n = 0, 2/0 is n = −1, 3/0 is n = −2 and 4/0 is n = −3.
For 12 AWG, the diameter is 0.127 × 92^(24 ÷ 39) ≈ 2.053 mm, or about 0.0808 inches. The cross-sectional area is π × (2.053 ÷ 2)² ≈ 3.31 mm².
Rules of thumb
Because AWG is logarithmic, a few patterns make it easy to estimate:
- Every 3 gauges roughly doubles or halves the cross-sectional area. 12 AWG has about twice the area of 15 AWG.
- Every 6 gauges roughly doubles or halves the diameter.
- Every 10 gauges changes the area, and the resistance, by about a factor of 10.
So 10 AWG has about 1.6 times the area of 12 AWG and a correspondingly lower resistance.
Common AWG sizes
| AWG | Diameter (mm) | Area (mm²) | Copper resistance (Ω/km) |
|---|---|---|---|
| 4/0 | 11.68 | 107.2 | 0.161 |
| 10 | 2.588 | 5.26 | 3.28 |
| 12 | 2.053 | 3.31 | 5.21 |
| 14 | 1.628 | 2.08 | 8.28 |
| 24 | 0.511 | 0.205 | 84.2 |
AWG and metric wire sizes
Outside North America, cable is usually sized by its cross-sectional area in square millimetres, such as 1.5 mm², 2.5 mm², 4 mm² and 6 mm². These sizes don't match AWG exactly. Some approximate equivalents:
- 1.5 mm² is between 16 AWG (1.31 mm²) and 15 AWG (1.65 mm²).
- 2.5 mm² is between 14 AWG (2.08 mm²) and 13 AWG (2.63 mm²).
- 4 mm² is between 12 AWG (3.31 mm²) and 11 AWG (4.17 mm²).
- 6 mm² is between 10 AWG (5.26 mm²) and 9 AWG (6.63 mm²).
When substituting one system for the other, choose a size with at least the required cross-sectional area. Never pick a smaller wire just because its gauge number looks close.
Solid and stranded wire
The AWG to mm converter gives the dimensions of a solid wire. Stranded wire of the same gauge has roughly the same copper area, but its overall diameter is slightly larger, because there are small gaps between the strands. Stranded wire is more flexible and is used where cables move or vibrate, while solid wire is common in fixed building wiring. When measuring a stranded conductor, it's more accurate to count and measure the individual strands than to measure the bundle.
A worked example
You have a cable whose conductor measures 1.6 mm across, and want to know its AWG size and resistance.
- Nearest gauge: 14 AWG, which is 1.628 mm.
- Area: about 2.08 mm², or 4.11 kcmil.
- Copper resistance: about 8.28 ohms per kilometre, or 2.53 ohms per 1,000 feet.
So 30 metres of this wire, out and back (60 metres of conductor), would have a resistance of about 0.5 ohms. Enter 1.6 mm in the AWG to mm converter to check.
Resistance and temperature
The resistance figures assume pure copper at 20 °C, using a resistivity of 1.724 × 10⁻⁸ ohm-metres, the international annealed copper standard. Copper's resistance rises by about 0.39% for each degree Celsius, so a wire at 60 °C has roughly 16% more resistance than at 20 °C. Aluminium has about 1.6 times the resistance of copper for the same size, which is why aluminium conductors are usually one or two sizes larger than copper ones carrying the same current.
Who uses an AWG to mm converter
Electricians use it when working with equipment or specifications from different countries. Electronics hobbyists and engineers use it to choose hook-up wire and check datasheets. Car audio, solar and RV installers use it for battery and power cables. Product teams and importers use it to state wire sizes clearly on product listings for international customers.
Need more customers from Google?
This tool is free and runs in your browser. If your business also needs more leads or sales, Google Ads is where people search with their wallet out. DeepRit is a Google Ads agency that does PPC and nothing else: we build the campaigns, block the searches that waste money, write the ads, set up conversion tracking and send you a short report every week. Request a free PPC audit and we will show you, in dollars, what we would fix first.
Ampacity is a separate question
The AWG to mm converter tells you the size of a wire, not how much current it can safely carry. That limit, called ampacity, depends on the insulation's temperature rating, how the cable is installed, the surrounding temperature, how many cables are bundled together, and local electrical codes. In North America, the National Electrical Code sets these limits for building wiring; other countries have their own standards. Always size building wiring using the applicable code tables, and ask a licensed electrician where required. To check voltage loss on a long run, use the voltage drop calculator.
kcmil and circular mils
For sizes larger than 4/0, wire is usually specified in thousands of circular mils, written kcmil (or MCM in older documents). A circular mil is the area of a circle one mil (0.001 inch) in diameter. A wire's area in circular mils is simply its diameter in mils squared, which made calculations easy before calculators. 4/0 AWG is 460 mils in diameter, so its area is 211,600 circular mils, or 211.6 kcmil. The next common size above 4/0 is 250 kcmil.
Common mistakes
- Assuming a higher gauge number means a thicker wire. It's the opposite.
- Measuring stranded wire across the bundle, which overstates the size.
- Treating 2.5 mm² and 14 AWG as identical. 14 AWG is smaller.
- Choosing wire by size alone without checking ampacity and code requirements.
Measuring a wire's gauge
To find the gauge of an unknown wire, strip a short length of insulation and measure the bare conductor with digital callipers or a micrometer, then enter the diameter in the AWG to mm converter. For stranded wire, measure one strand, count the strands, and add up their areas: a conductor of 7 strands each 0.65 mm across has a total area of about 7 × π × 0.325² ≈ 2.32 mm², which is a little more than 14 AWG. Inexpensive wire gauge tools with labelled slots are also available, but they're designed for solid wire. The printing on the cable's insulation usually states the size, so check there first.
Speaker and audio cable
Speaker cable is often sold by AWG, typically 12, 14, 16 or 18 AWG. Thicker cable (a lower gauge number) has lower resistance, which matters most for long runs and for low-impedance speakers. As a rough guide, the resistance of the cable should be small compared with the speaker's impedance. For example, 10 metres of 16 AWG cable, which is 20 metres of conductor out and back, has a resistance of about 0.26 ohms, around 3% of an 8-ohm speaker. For long runs or 4-ohm speakers, a thicker cable keeps losses lower.
Network and data cables
Ethernet cables usually use 22 to 24 AWG conductors in permanent installations and 24 to 28 AWG in thinner patch cables. Thinner conductors have more resistance, which matters for Power over Ethernet, where cables also carry power to cameras, phones and access points.
Sources and further reading
- American wire gauge on Wikipedia: the formula, table and history.
- Circular mil on Wikipedia: the area unit used for large conductors.
- Electrical resistivity and conductivity on Wikipedia: resistivity of copper and aluminium.
Frequently asked questions
How do I convert AWG to mm?
Diameter (mm) = 0.127 × 92^((36 − gauge) ÷ 39). 12 AWG is about 2.05 mm.
What is 4/0 wire in mm?
About 11.68 mm in diameter and 107.2 mm² in area.
Is 2.5 mm² the same as 14 AWG?
No. 14 AWG is about 2.08 mm²; 2.5 mm² sits between 14 and 13 AWG.
Why does a higher AWG number mean thinner wire?
The numbers originally counted how many times wire was drawn through dies to make it thinner.
How much current can a wire carry?
That depends on insulation, installation and local codes, not just size. Check the applicable code tables.
Is the AWG to mm converter free?
Yes. It's free, needs no sign-up, and works in your browser.