Watts to Amps Calculator (DC, AC and 3-Phase)

A free tool by DeepRit, a Google Ads agency that does PPC and nothing else. We build and run Google Ads accounts so every click is accounted for. Book a free audit call

Convert watts to amps (and amps to watts) for DC, single-phase AC and three-phase AC, with voltage and power factor. Formulas and examples included.

Apparent power (VA)
0

Free, no sign-up. Runs in your browser: nothing you type is uploaded or saved.

How to use the watts to amps calculator

  1. Choose the direction: watts to amps, or amps to watts.
  2. Choose the circuit type: DC, AC single-phase, or AC three-phase.
  3. Enter the power in watts (or the current in amps).
  4. Enter the voltage. For three-phase, use the line-to-line voltage (for example 208, 400 or 480 V).
  5. Enter the power factor for AC circuits. Use 1 for purely resistive loads like heaters, kettles and incandescent bulbs. Motors and some electronics have lower power factors, often around 0.8 to 0.95; check the device's label or datasheet.

The watts to amps calculator shows the current (or power), the apparent power in volt-amperes (VA), and a table of common wattages at your voltage.

The formulas

DC

Amps = watts ÷ volts

A 120 W device on a 12 V DC supply draws 120 ÷ 12 = 10 A.

AC single-phase

Amps = watts ÷ (power factor × volts)

A 1,500 W heater (power factor 1) on 120 V draws 1,500 ÷ 120 = 12.5 A. On 230 V, the same heater draws 6.5 A.

AC three-phase

Amps = watts ÷ (√3 × power factor × line-to-line volts)

A 10 kW motor with a power factor of 0.85 on 400 V three-phase draws 10,000 ÷ (1.732 × 0.85 × 400) = 17 A.

Amps to watts

Rearrange: watts = volts × amps for DC; watts = power factor × volts × amps for single-phase AC; and watts = √3 × power factor × volts × amps for three-phase.

Why you can't convert watts to amps without volts

Watts measure power, amps measure current and volts measure electrical pressure. Power = voltage × current, so the same wattage draws very different currents at different voltages: 1,200 W is 10 A at 120 V but only 5.2 A at 230 V. That's why the watts to amps calculator always needs the voltage.

Common household voltages

  • North America: 120 V for most outlets; 240 V for large appliances like dryers and ranges.
  • Europe, UK, much of Asia, Africa and Australia: 220 to 240 V (230 V nominal in Europe).
  • Japan: 100 V.
  • Car and RV electrics: 12 V DC (24 V for many trucks).
  • USB: 5 V, with higher voltages for fast charging.

Power factor

In AC circuits, some devices draw current that isn't perfectly in step with the voltage. The power factor (between 0 and 1) measures how effectively the current is turned into useful work:

  • Real power (watts): the power that does work.
  • Apparent power (volt-amperes, VA): volts × amps.
  • Power factor = watts ÷ VA.

A device with a power factor of 0.8 that uses 800 W draws 1,000 VA, so the current is higher than the wattage alone suggests. Generators, UPS units and some cables are rated in VA or kVA for this reason. The watts to amps calculator shows the VA figure too.

Wattage and current of common appliances

These are typical ranges; check your appliance's label for its exact rating.

Appliance Typical watts Amps at 120 V Amps at 230 V
LED bulb 9 0.08 0.04
Laptop charger 65 0.54 0.28
Microwave 1,000 8.3 4.3
Kettle 1,500 to 3,000 12.5 to 25 6.5 to 13
Space heater 1,500 12.5 6.5
Hair dryer 1,800 15 7.8

Choosing circuits, breakers and extension cords

Knowing the current helps you avoid overloading circuits:

  • Add up the current of everything on a circuit that might run at the same time.
  • Continuous loads: in the US, the National Electrical Code generally sizes circuits so continuous loads (running three hours or more) don't exceed 80% of the breaker rating. A 15 A circuit should carry no more than 12 A continuously, and a 20 A circuit no more than 16 A.
  • Extension cords: check the cord's rating in amps or watts. Undersized cords can overheat.
  • Generators and inverters: compare the total watts and VA, and allow extra for motors that draw a surge when starting.

The watts to amps calculator shows the minimum circuit rating for a continuous load as a guide. For any wiring work, follow local codes and use a licensed electrician.

A worked example

Priya wants to run a 1,500 W space heater and a 1,000 W microwave from the same 120 V kitchen circuit protected by a 20 A breaker.

In the watts to amps calculator: heater = 12.5 A, microwave = 8.3 A. Together, 20.8 A, which is more than the 20 A breaker allows, so the breaker would trip. She moves the heater to a different circuit.

For her garden workshop, she checks a 2,200 W table saw on 230 V with a power factor of about 0.9: 2,200 ÷ (0.9 × 230) = 10.6 A, within the capacity of a 16 A circuit.

Who uses a watts to amps calculator

Homeowners use it to avoid tripping breakers and to choose extension cords and generators. Electricians and engineers use it for load calculations. RV owners, boaters and off-grid users use it for 12 V systems, inverters and batteries. Students use it to learn the relationship between power, voltage and current.

Need more customers from Google?

This tool is free and runs in your browser. If your business also needs more leads or sales, Google Ads is where people search with their wallet out. DeepRit is a Google Ads agency that does PPC and nothing else: we build the campaigns, block the searches that waste money, write the ads, set up conversion tracking and send you a short report every week. Request a free PPC audit and we will show you, in dollars, what we would fix first.

Watts to amps conversion table

Quick conversions for resistive loads (power factor 1):

Watts Amps at 12 V DC Amps at 120 V Amps at 230 V Amps at 240 V
100 8.33 0.83 0.43 0.42
500 41.67 4.17 2.17 2.08
1,000 83.33 8.33 4.35 4.17
1,500 125 12.5 6.52 6.25
2,000 166.67 16.67 8.70 8.33
3,000 250 25 13.04 12.5

The 12 V column shows why low-voltage systems need thick cables: the same power needs ten times the current of a 120 V circuit.

Inverters and batteries

When you run AC appliances from a battery through an inverter, the battery supplies much more current than the appliance draws on the AC side. A 1,000 W appliance on a 12 V system draws about 83 A from the battery, plus extra for the inverter's losses (often 10% to 15%), so roughly 92 to 96 A. A 100 Ah battery would run it for well under an hour in practice, because batteries shouldn't be fully drained and capacity falls at high currents. Use the watts to amps calculator with DC and 12 V (or 24 or 48 V) to size cables, fuses and batteries.

Kilowatts and kVA

Large equipment and generators are often rated in kilowatts (kW) or kilovolt-amperes (kVA). 1 kW = 1,000 W. For a generator rated at 5 kVA with a power factor of 0.8, the real power available is 5 × 0.8 = 4 kW. For a three-phase 400 V supply, 10 kVA corresponds to about 14.4 A per phase (10,000 ÷ (1.732 × 400)). The watts to amps calculator shows both watts and VA so you can compare equipment ratings with generator and UPS ratings.

Starting current

Motors in fridges, air conditioners, pumps and power tools draw several times their running current for a moment when they start. That surge doesn't usually trip a breaker, but it matters when sizing generators and inverters, which must handle the peak. Manufacturers often list a "starting" or "surge" wattage separately from the running wattage.

Reading appliance labels

Most appliances have a rating label, usually on the back or underneath, listing the voltage, frequency (50 or 60 Hz) and either the power in watts or the current in amps, sometimes both. If the label gives only amps, multiply by the voltage to estimate the watts for resistive loads, or switch the watts to amps calculator to "Amps → watts". Labels show the maximum rating; many devices use less most of the time. Heating appliances like kettles, toasters and heaters usually run close to their rated power whenever they're on, while computers, TVs and fridges vary.

Solar panels and batteries

Solar systems combine DC and AC calculations. Panels and batteries work in DC at 12, 24 or 48 V, and inverters convert to AC for household appliances. Higher system voltages mean lower currents for the same power, which allows thinner cables and smaller losses, which is why larger off-grid systems often use 48 V.

Sources and further reading

Frequently asked questions

How do I convert watts to amps?

For DC, divide watts by volts. For single-phase AC, divide watts by (power factor × volts). For three-phase, divide by (√3 × power factor × volts).

How many amps is 1500 watts?

12.5 A at 120 V, or about 6.5 A at 230 V (power factor 1).

How many watts can a 15 amp circuit handle?

1,800 W at 120 V in total, or about 1,440 W for continuous loads at 80%.

How many amps is 1000 watts at 230 volts?

About 4.35 A.

Why do I need the power factor?

For AC devices like motors, the current is higher than watts ÷ volts. The power factor accounts for that.

Is the watts to amps calculator free?

Yes. It's free, needs no sign-up, and works in your browser.

Free PPC audit

See where your ad budget leaks.

We look at your Google Ads account before the call, then walk you through what we'd fix first, in dollars. No obligation, no hard sell.

Book a free audit call 30-minute call · Free · The audit is yours to keep