kVA to kW Converter (With Power Factor)
A free tool by DeepRit, a Google Ads agency that does PPC and nothing else. We build and run Google Ads accounts so every click is accounted for. Book a free audit call
Convert kVA to kW with the power factor, or kW to kVA, plus kVAR and the current for single or three phase. kW = kVA × power factor.
- Reactive power (kVAR)
- 0
- Current
- 0
Free, no sign-up. Runs in your browser: nothing you type is uploaded or saved.
How to use the kVA to kW converter
- Enter the power in kVA, or in kW if you're converting the other way.
- Choose the direction: kVA to kW, or kW to kVA.
- Enter the power factor, a number between 0 and 1. If you don't know it, 0.8 is the standard figure used to rate most generators.
- Optionally, enter the voltage and choose single or three phase to see the current in amps.
The kVA to kW converter shows the converted power, the reactive power in kVAR, and the current if you entered a voltage.
What is the difference between kVA and kW?
In an AC (alternating current) electrical system, there are three related kinds of power:
- Real power (kW): the power that does useful work, such as turning a motor, heating an element or lighting a lamp. It's measured in watts or kilowatts.
- Apparent power (kVA): the total power the supply has to deliver, combining real power and reactive power. It's measured in volt-amperes or kilovolt-amperes.
- Reactive power (kVAR): power that flows back and forth to build magnetic and electric fields in equipment like motors, transformers and fluorescent lighting. It does no useful work but still loads the wires and the supply.
Apparent power is the combination of the other two, and the three form a right-angled triangle, often called the power triangle:
kVA² = kW² + kVAR²
The power factor
The power factor (PF) is the ratio of real power to apparent power:
PF = kW ÷ kVA
So:
kW = kVA × PF
kVA = kW ÷ PF
For a purely resistive load, like an electric heater or a kettle, the power factor is 1, and kW equals kVA. For loads with motors or transformers, the power factor is lower, often between about 0.7 and 0.95. For example, 100 kVA at a power factor of 0.8 delivers 80 kW of real power, with 60 kVAR of reactive power, because √(100² − 80²) = 60.
Why generators are rated in kVA
Generators and transformers are usually rated in kVA because the heat in their windings depends on the total current, whatever the power factor of the load. A generator's engine, though, has to supply the real power. That's why generator ratings often show both: for example, "100 kVA / 80 kW", which assumes a power factor of 0.8. When sizing a generator, add up the kW of everything it needs to run, allow extra for motors that draw a high current when starting, then divide by the power factor to get the kVA rating you need. The kVA to kW converter does that last step.
Calculating current
Current depends on the apparent power, not just the real power. The kVA to kW converter calculates:
- Single phase: amps = kVA × 1,000 ÷ voltage.
- Three phase: amps = kVA × 1,000 ÷ (√3 × line voltage).
For example, 100 kVA on a 400 V three-phase supply draws about 100,000 ÷ (1.732 × 400) ≈ 144 A per phase. On a 230 V single-phase supply, 10 kVA draws about 43.5 A. These figures help with sizing cables, breakers and other equipment, although the final choice must follow your local electrical code and should be made by a qualified electrician.
A worked example
A workshop needs to run machines using 64 kW in total, with an overall power factor of 0.8.
- Apparent power: 64 ÷ 0.8 = 80 kVA.
- Reactive power: √(80² − 64²) = 48 kVAR.
- Current at 400 V three phase: 80,000 ÷ (1.732 × 400) ≈ 115.5 A.
A generator or supply rated at 80 kVA would be just enough for the steady load; a margin above that is sensible to cover starting currents and future needs. Choose "kW → kVA" in the kVA to kW converter, enter 64, a power factor of 0.8 and 400 V three phase to check.
Improving the power factor
A low power factor means more current flows for the same useful work, which increases losses in cables and transformers and can lead to extra charges from electricity suppliers for larger commercial customers. Businesses often improve their power factor by installing capacitor banks, which supply reactive power locally, or by using modern equipment with built-in power factor correction. Raising the power factor from 0.75 to 0.95 reduces the current needed for the same kW by about 21%.
Who uses a kVA to kW converter
Electricians and electrical engineers use it to size generators, transformers, UPS systems and cables. Facility managers use it to compare equipment ratings and understand electricity bills. Generator and UPS sellers use it to explain ratings to customers. Students use it to learn about AC power.
Need more customers from Google?
This tool is free and runs in your browser. If your business also needs more leads or sales, Google Ads is where people search with their wallet out. DeepRit is a Google Ads agency that does PPC and nothing else: we build the campaigns, block the searches that waste money, write the ads, set up conversion tracking and send you a short report every week. Request a free PPC audit and we will show you, in dollars, what we would fix first.
UPS ratings
Uninterruptible power supplies (UPS) are also rated in both VA and W. A UPS rated "1,500 VA / 900 W" has an implied power factor of 0.6, while a newer model might be "1,500 VA / 1,350 W", a power factor of 0.9. When choosing a UPS, make sure both the VA rating and the watt rating are above what your equipment needs. Computers and servers with modern power supplies typically have power factors close to 1, so their watt figure is the one that usually limits the choice.
kW, kVA and horsepower
Motors are often rated in kilowatts or horsepower of mechanical output. To find the electrical supply a motor needs, divide its output by its efficiency to get the electrical kW, then divide by its power factor to get kVA. A 15 kW motor with 90% efficiency and a power factor of 0.85 draws about 15 ÷ 0.9 ÷ 0.85 ≈ 19.6 kVA. To convert horsepower to kilowatts first, use the kW to hp converter.
Common mistakes
- Treating kVA and kW as the same for motor and mixed loads.
- Forgetting starting current, which can be several times the running current for motors.
- Using phase voltage instead of line voltage in three-phase calculations.
- Assuming a power factor without checking equipment data when accuracy matters.
Solar inverters and kVA
Solar and battery inverters are often rated in both kW and kVA. Some inverters can supply reactive power to help support the grid, so their kVA rating is higher than their kW rating. Others list the same number for both, because they're designed to run at a power factor close to 1. When comparing inverters, or checking whether one is allowed under your grid connection rules, look at both ratings. The solar panel calculator helps estimate the system size in kW.
Transformers
Distribution transformers are rated in kVA, for example 500 kVA or 1,000 kVA. The real power they can deliver depends on the power factor of the buildings they supply. A 500 kVA transformer serving a load with a power factor of 0.9 can deliver up to 450 kW. If the power factor falls to 0.75, the same transformer can only deliver 375 kW before it reaches its rating. That's another reason businesses with large motor loads invest in power factor correction: it frees up capacity in transformers and cables that would otherwise be used by reactive power.
Electricity bills and kVA charges
Some electricity tariffs for larger businesses include a capacity or demand charge based on kVA rather than kW, and some add a charge for reactive power. On those tariffs, improving the power factor can lower the bill even if the real energy used stays the same. If your bill shows kVA, kVAR or power factor figures, the kVA to kW converter helps you see how much of your supply capacity is used by real power.
Single phase versus three phase
Homes in many countries have a single-phase supply, typically around 230 V in Europe and much of the world, or split-phase 120/240 V in North America. Commercial and industrial buildings often have three-phase supplies, commonly 400 V in Europe and 208 V or 480 V in North America. Three-phase power delivers more power over the same size of cable and suits large motors. When entering a voltage in the kVA to kW converter, use the line-to-line voltage for three phase.
Sources and further reading
- Power factor on Wikipedia: real, reactive and apparent power and the power triangle.
- Volt-ampere on Wikipedia: the unit of apparent power and why equipment is rated in it.
- Three-phase electric power on Wikipedia: line voltages and the √3 factor.
Frequently asked questions
How do I convert kVA to kW?
Multiply kVA by the power factor: kW = kVA × PF.
How many kW is 100 kVA?
At a power factor of 0.8, 80 kW. At a power factor of 1, 100 kW.
What power factor should I use?
Use the figure from the equipment's data. For generator ratings, 0.8 is standard.
Why are generators rated in kVA?
Because their heating depends on total current, which depends on apparent power, not just real power.
How do I calculate amps from kVA?
Single phase: kVA × 1,000 ÷ volts. Three phase: kVA × 1,000 ÷ (√3 × volts).
Is the kVA to kW converter free?
Yes. It's free, needs no sign-up, and works in your browser.